- Input
- 12 to 24 volt AC or DC operation (setting not required), (0.4A @ 12volt, 0.2A @ 24 volt current consumption with all relays energized).
- Power supply input options:
- a) One (1) common power input (board and lock power).
- b) Two (2) isolated power inputs (one (1) for board power and one (1) for lock/accessory power).
- Four (4) Access Control System trigger inputs:
- a) Four (4) normally open (NO) inputs.
- b) Four (4) open collector sink inputs.
- c) Any combination of the above.
- Output
- Four (4) independently controlled outputs:
- a) Four (4) Fail-Safe and/or Fail-Secure power outputs.
- b) Four (4) dry form "C" 5A rated relay outputs
- c) Any combination of the above
- Four (4) auxiliary power outputs (unswitched).
- Output ratings:
- Fuses are rated 2.5A each.
- Main fuse is rated at 10A.
- Note: Total output current is determined by the power supply, not to exceed a maximum of 10A. total.
- Features
- Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the four (4) outputs.
- Fire Alarm disconnect input options:
- a) Normally open (NO) or normally closed (NC) dry contact input.
- b) Polarity reversal input from FACP signaling circuit.
- FACP output relay (form "C" contact rated @ 1A 28VDC not evaluated by UL).
- Removable terminal blocks facilitate ease of installation.
- Visual Indicators
- Red LEDs indicate outputs are triggered (relays energized).
- Green LED indicates FACP disconnect is triggered.
- Electrical
- Temperature:
- Operating: 0° C to 49° C (32° F to 120° F).
- Storage: - 20° C to 70° C ( - 4° F to 158° F).
- Relative Humidity 85% +/- 5%.
- BTU/Hr (approx.):
- 12VDC or 12VAC: 2 BTU/Hr.
- 24VDC or 24VAC: 3 BTU/Hr.